DRW170776AA
DUAL INDICATOR TEMPERATURE CONTROLLER
TCN4 SERIES
I N S T R U C T I O N M A N U A L
Thank you for choosing our Autonics product.
Please read the following safety considerations before use.
Safety Considerations
※Please observe all safety considerations for safe and proper product operation to avoid hazards.
※Safety considerations are categorized as follows.
Warning Failure to follow these instructions may result in serious injury or death.
Caution Failure to follow these instructions may result in personal injury or product damage.
※The symbols used on the product and instruction manual represent the following
symbol represents caution due to special circumstances in which hazards may occur.
Warning
1. Fail-safe device must be installed when using the unit with machinery that may cause
serious injury or substantial economic loss. (e.g. nuclear power control, medical equipment,
ships, vehicles, railways, aircraft, combustion apparatus, safety equipment, crime/disaster
prevention devices, etc.)
Failure to follow this instruction may result in fire, personal injury, or economic loss.
2. Install on a device panel to use.
Failure to follow this instruction may result in electric shock or fire.
3. Do not connect, repair, or inspect the unit while connected to a power source.
Failure to follow this instruction may result in electric shock or fire.
4. Check ‘Connections’ before wiring.
Failure to follow this instruction may result in fire.
5. Do not disassemble or modify the unit.
Failure to follow this instruction may result in electric shock or fire.
Caution
1. When connecting the power input and relay output, use AWG 20(0.50mm
2
) cable or over and
tighten the terminal screw with a tightening torque of 0.74~0.90N . m.
When connecting the sensor input and communication cable without dedicated cable, use
AWG 28~16 cable and tighten the terminal screw with a tightening torque of 0.74~0.90N . m.
Failure to follow this instruction may result in fire or malfunction due to contact failure.
2. Use the unit within the rated specifications.
Failure to follow this instruction may result in fire or product damage.
3. Use dry cloth to clean the unit, and do not use water or organic solvent.
Failure to follow this instruction may result in electric shock or fire.
4. Do not use the unit in the place where flammable/explosive/corrosive gas, humidity, direct
sunlight, radiant heat, vibration, impact, or salinity may be present.
Failure to follow this instruction may result in fire or explosion.
5. Keep metal chip, dust, and wire residue from flowing into the unit.
Failure to follow this instruction may result in fire or product damage.
Ordering Information
T
CN
4 S
2 4 R
P
No-mark Bolt wiring method
Wiring method
P
Connector plug connection method
Control output
R
Relay contact + SSR drive output
2
24VAC 50/60Hz, 24-48VDC
Power supply
4
100-240VAC 50/60Hz
Sub output
2
Alarm1 + Alarm2 output
S
DIN W48 × H48mm
M
DIN W72 × H72mm
Size
H
DIN W48 × H96mm
L
DIN W96 × H96mm
Digit
4
9999 (4 digit)
Setting type
CN
Dual display type, set by touch switch
Item
T
Temperature controller
1: Only for TCN4S model.
2: In case of the AC voltage model, SSR drive output method (standard ON/OFF control, cycle
control, phase control) is available to select.
※ The above specifications are subject to change and some models may be discontinued
without notice.
※ Be sure to follow cautions written in the instruction manual and the technical descriptions
(catalog, homepage).
Specification
Series
TCN4S
TCN4M
TCN4H
Power
AC Power
100-240VACᜠ 50/60Hz
supply
AC/DC Power 24VACᜠ 50/60Hz, 24-48VDCᜡ
Allowable voltage range 90 to 110% of rated voltage
AC Power
Max. 5VA(100-240VAC 50/60Hz)
Power
consumption
AC/DC Power Max. 5V(24VAC 50/60Hz), Max. 3W(24-48VDC)
Display method
7 segment (PV: red, SV: green), other display part(green, red) LED method
PV(W×H)
7.0×15.0mm
9.5×20.0mm
7.0×14.6mm
Character
size
SV(W×H)
5.0×9.5mm
7.5×15.0mm
6.0×12.0mm
RTD
DIN Pt100Ω, Cu50Ω (Allowable line resistance max.5Ω per a wire)
Input
type
TC
K(CA), J(IC), L(IC), T(CC), R(PR), S(PR)
Display
RTD
At room temperature(23ºC ± 5ºC): (PV ± 0.5% or ±1ºC, select the higher one) ± 1 digit
accuracy
Out of room temperature range: (PV± 0.5% or ±2ºC, select the higher one)± 1digit
TC
1
For TCN4S- -P, add ±1℃ by accuracy standard.
Control
Relay
250VACᜠ 3A 1a
output
SSR
12VDCᜡ±2V 20mA Max.
Alarm output
AL1, AL2 Relay: 250VACᜠ 1A 1a
Control method
ON/OFF control, P, PI, PD, PID control
1 to 100℃/℉ (0.1 to 50.0℃/℉)
Hysteresis
Proportional band(P)
0.1 to 999.9ºC/℉
Integral time(I)
0 to 9999 sec.
Derivative time(D)
0 to 9999 sec.
Control period(T)
0.5 to 120.0 sec.
Manual reset
0.0 to 100.0%
Sampling period
100ms
AC power
2000VAC 50/60Hz 1min.(between input terminal and power terminal)
Dielectric
strength
AC/DC power 1000VAC 50/60Hz 1min.(between input terminal and power terminal)
Vibration
0.75mm amplitude at frequency of 5 to 55Hz in each X, Y, Z direction for 2 hours
Mechanical OUT: Over 5,000,000 times, AL1/2: Over 5,000,000 times
Relay life
OUT: Over 200,000 times(250VAC 3A resistive load)
cycle
Electrical
AL1/2: Over 300,000 times(250VAC 1A resistive load)
Insulation resistance
Min. 100MΩ(at 500VDC megger)
Noise
Square-wave noise by noise simulator(pulse width 1㎲) ±2KV R-phase and S-phase
Memory retention
Approx. 10 years (when using non-volatile semiconductor memory type)
Ambient temp. -10 to 50ºC, Storage: -20 to 60ºC
Environ
-ment
Ambient humi. 35 to 85%RH, Storage: 35 to 85%RH
Double insulation or reinforced insulation (mark:
Insulation type
the measuring input part and the power part : AC power 2kV, AC/DC power 1kV)
Approval
Approx. 147g
Approx. 203g
Approx. 194g
Weight
2
(approx. 100g)
(approx. 133g)
(approx. 124g)
1:
At room temperature(23ºC±5ºC)
— Below 200ºC of thermocouple R(PR), S(PR) is (PV ±0.5% or ±3ºC, select the higher one) ±1 digit
— Over 200ºC of thermocouple R(PR), S(PR) is (PV ±0.5% or ±2ºC, select the higher one) ±1 digit
— Termocouple L (IC), RTD Cu50Ω is (PV ±0.5% or ±2ºC, select the higher one) ±1 digit
Out of room temperature range
— Below 200ºC of thermocouple R(PR), S(PR) is (PV ±1.0% or ±6ºC, select the higher one) ±1 digit
— Over 200ºC of thermocouple R(PR), S(PR) is (PV ±0.5% or ±5ºC, select the higher one) ±1 digit
— Thermocouple L(IC), RTD Cu50Ω is (PV ±0.5% or ±3ºC, select the higher one) ±1 digit
For TCN4S- -P, add ±1℃ by accuracy standard.
2: The weight includes packaging. The weight in parentheses is for unit only.
Environment resistance is rated at no freezing or condensation.
Unit Description
1. Present temperature (PV) display (Red)
1) RUN mode: Present temperature (PV) display
2) Parameter setting mode: Parameter display
2. Set temperature (SV) display (Green)
1) RUN mode: Set temperature (SV) display
1
2) Parameter setting mode
: Parameter setting value display
3. Control/Alarm output display indicator
8
1) OUT: It turns ON when the control output is ON.
3
During SSR drive output type in CYCLE/
2
PHASE control, this indicator turns ON when
7
MV is over 3.0%.
4
2) AL1/AL2: It turns ON when the alarm output is ON.
5
4. Auto tuning indicator
AT indicator flashes by every 1 sec during operating
auto tuning.
5.
key
6
Used when entering into parameter groups,
returning to RUN mode, moving parameter, and saving
setting values.
6. Adjustment
Used when entering into set value change mode, digit moving and digit up/down.
1
7. Digital input key
2
Press
keys for 3 sec. to operate the set function
(RUN/STOP, alarm output reset, auto tuning) in digital input key [DI-T].
8. Temperature unit (
/℉) indicator
ºC
It shows current temperature unit.
Input Sensor and Temperature Range
Input sensor
Display
Temperature range(
-50 to 1200
KCaH
K(CA)
-50.0 to 999.9
KCaL
JIcH
-30 to 800
J(IC)
JIcL
-30.0 to 800.0
-40 to 800
LIcH
Thermocouple
L(IC)
-40.0 to 800.0
LIcL
TCcH
-50 to 400
T(CC)
TCcL
-50.0 to 400.0
R(PR)
0 to 1700
RPR
S(PR)
0 to 1700
SPR
DPtH
-100 to 400
DPt100Ω
-100.0 to 400.0
DPtL
RTD
-50 to 200
CUsH
Cu50Ω
CUsL
-50.0 to 200.0
Dimensions
TCN4L
TCN4S Series
48
6
64.5
11.0×22.0mm
7.0×14.0mm
TCN4H Series
6
64.5
48
Bracket
TCN4S Series
TCN4M, TCN4H, TCN4L Series
31
48.6
20
5
45
, dielectric strength between
15
21
Approx. 275g
55
(approx. 179g)
56
Connections
1)TCN4S Series
AL1 OUT
SSR
250VAC
OUT
※1
1A 1a
AL2 OUT
250VAC
1A 1a
Relay OUT
B’
250VAC
3A 1a
B
A
RTD
※2
SOURCE
2)TCN4S- -P
SSR
※1
OUT
Relay OUT
250VAC
3A 1a
※2
SOURCE
ºC
) Temperature range(℉)
※ TCN4 Series has selectable control output; Relay output, and
-58 to 2192
SSR drive output. AC/DC voltage type does not have SSRP
-58.0 to 999.9
function.
※1: 12VDC±2V 20mA Max.
-22 to 1472
※2: AC voltage type: 100-240VAC 5VA 50/60Hz
-22.0 to 999.9
AC/DC voltage type: 24VAC 5VA 50/60Hz
-40 to 1472
24-48VDC 3W
(unit: mm)
-40 to 999.9
※Use crimp terminals or teminals of size specified below.
Terminal
a
-58 to 752
a
b
c
number
-58.0 to 752.0
1 to 8
6
Max. 1.7 Max. 3.7
c
b
32 to 3092
9 to 11
6 to 8 Max. 2.1 Max. 4.2
<Crimp terminal>
12 to 14 6 to 8 Max. 1.5 Max. 3.5
32 to 3092
-148 to 752
a b
a b
-148.0 to 752.0
<Round>
<Forked>
-58 to 392
a
Min. 3.0
Min. 3.0
-58.0 to 392.0
b
Max.5.8
Max.5.8
TCN4S- -P
6
56
11.5
48
1.7
TCN4L Series
96
6
64.5
Panel cut-out
A
C
46
Size
A
B
C
D
Series
TCN4S
Min. 65
Min. 65
45
45
0.6
0
TCN4M
Min. 90
Min. 90
68
68
0.7
0
12
TCN4H
Min. 65
Min. 115
45
0.6
92
0
23.9
TCN4L
Min. 115
Min. 115
92
92
0.8
0
Parameter Groups
3)TCN4M Series
1. All Parameter
Please any key among
,
,
,
SV setting
Parameter 1group
AL1 OUT
SSR
250VAC
OUT
※1
1A 1a
AL1 alarm termerature
TC
AL2 OUT
250VAC
1A 1a
AL2 alarm termerature
Relay OUT
B’
250VAC
3A 1a
B
+
TC
A
+
RTD
SOURCE
※2
4)TCN4H/L Series
AL1 OUT
250VAC
1A 1a
AL2 OUT
250VAC
1A 1a
B’
B
TC
A
RTD
AL1 OUT
250VAC
SSR
1A 1a
※1
OUT
AL2 OUT
Press
key over 3 sec in any parameter group, it saves the set value and returns to RUN mode.
250VAC
Relay OUT
1A 1a
(Exception: Press
250VAC
If no key entered for 30 sec., it returns to RUN mode automatically and the set value of parameter
TC
RTD
3A 1a
B’
is not be saved.
Press
key again within 1 sec. after returning to RUN mode, it advances of the first parameter
B
of previous parameter group.
A
Press
key to move next parameter.
Parameter marked in
Set parameter as ‘Parameter 2 group → Parameter 1 group → Setting group of set value’ order
SOURCE
※2
considering parameter relation of each setting group.
1: It is not displayed for AC/DC power model (TCN4 -22R).
(unit: mm)
TCN4M Series
72
6
64.5
Terminal cover(sold separately)
RSA-COVER(48×48mm)
RMA-COVER(72×72mm)
70
3
48.4
9.8
22.5
RHA-COVER(48×96mm)
RLA-COVER(96×96mm )
47.2
4
94
3
0.6
0
0.7
0
0.8
0
0.8
0
Run mode
2sec.
4sec.
Parameter 2group
PAR1
PAR2
Input
Temperature
Input
Input
sensor
unit
correction
digital filter
AL1
IN-T
UNIT
IN-B
MAvF
AL2
Control output
SV high-
SV low-limit
Control type
operation
limit value
value
Auto tunung
C-MD
O-FT
H-SV
L-SV
AT
Proportional band
SSR drive output
Control output
Control
AL1 alarm
method
※1
P
type
cycle
operation mode
OUT
SSrM
T
AL-1
Integral time
I
LBA detection
LBA
Alarm output
AL2 alarm
band
monitoring time
hysteresis
operation mode
Derivative time
LBaT
AHYS
AL-2
LBaB
D
Manual reset
REST
Digital input
Control output MV in case
Parameter
key
of input break error
lock
DI-K
ErMV
LOC
Hysteresis
HYS
3sec.
3sec.
key once in SV setting group, it returns to RUN mode).
might not be displayed depending on other parameter settings.
File Specifications:895/895240-tcn4s_series.pdf file (17 Jul 2023) |
Accompanying Data:
Autonics TCN4S Series Temperature Controller PDF Manual (Updated: Monday 17th of July 2023 05:47:01 AM)
Rating: 4.9 (rated by 57 users)
Compatible devices: TX4S Series, TZ4H Series, TC4Y, TCN4S, TM-Q02H, TC Series, TCN Series, TR1D Series.
Recommended Documentation:
Manual (Text Version):
(Ocr-Read Summary of Contents of some pages of the Autonics TCN4S Series Document (Main Content), UPD: 17 July 2023)
-
1, DUAL INDICATOR TEMPERATURE CONTROLLER TCN4 SERIES M A N U A L Thank you very much for selecting Autonics products. For your safety, please read the following before using. 1. In case of using this unit with machinery (Ex: nuclear power control, medical equipment, ship, vehicle, train, airplane, combustion apparatus, safety device, crime/disaster prevention equipment, etc) which may cause damag…
-
2, EP-KE-03-0350 Major product Parameter Display Description Input sensor IN-T Setting range: Refer to ‘Input sensor and temperature range’. If changing input sensor, SV , IN-B , H-SV , L-SV , AL1 , AL2 , LBaT , LBaB parameter values are initialized. Temperature unit UNIT ?C ?F If changing temperature unit , SV , IN-B , H-SV , L-SV , AL1 , AL2 , LBaT , LBaB parameter …
-
Autonics TCN4S Series User Manual
-
Autonics TCN4S Series User Guide
-
Autonics TCN4S Series PDF Manual
-
Autonics TCN4S Series Owner’s Manuals
Recommended: W6-LI Pentium Pro PCI/ISA, MPV 520 W, DRIFTER, 850, System Three
Links & Tools
Operating Impressions, Questions and Answers:
DRW170776AA
DUAL INDICATOR TEMPERATURE CONTROLLER
TCN4 SERIES
I N S T R U C T I O N M A N U A L
Thank you for choosing our Autonics product.
Please read the following safety considerations before use.
Safety Considerations
※Please observe all safety considerations for safe and proper product operation to avoid hazards.
※Safety considerations are categorized as follows.
Warning Failure to follow these instructions may result in serious injury or death.
Caution Failure to follow these instructions may result in personal injury or product damage.
※The symbols used on the product and instruction manual represent the following
symbol represents caution due to special circumstances in which hazards may occur.
Warning
1. Fail-safe device must be installed when using the unit with machinery that may cause
serious injury or substantial economic loss. (e.g. nuclear power control, medical equipment,
ships, vehicles, railways, aircraft, combustion apparatus, safety equipment, crime/disaster
prevention devices, etc.)
Failure to follow this instruction may result in fire, personal injury, or economic loss.
2. Install on a device panel to use.
Failure to follow this instruction may result in electric shock or fire.
3. Do not connect, repair, or inspect the unit while connected to a power source.
Failure to follow this instruction may result in electric shock or fire.
4. Check ‘Connections’ before wiring.
Failure to follow this instruction may result in fire.
5. Do not disassemble or modify the unit.
Failure to follow this instruction may result in electric shock or fire.
Caution
1. When connecting the power input and relay output, use AWG 20(0.50mm
2
) cable or over and
tighten the terminal screw with a tightening torque of 0.74~0.90N . m.
When connecting the sensor input and communication cable without dedicated cable, use
AWG 28~16 cable and tighten the terminal screw with a tightening torque of 0.74~0.90N . m.
Failure to follow this instruction may result in fire or malfunction due to contact failure.
2. Use the unit within the rated specifications.
Failure to follow this instruction may result in fire or product damage.
3. Use dry cloth to clean the unit, and do not use water or organic solvent.
Failure to follow this instruction may result in electric shock or fire.
4. Do not use the unit in the place where flammable/explosive/corrosive gas, humidity, direct
sunlight, radiant heat, vibration, impact, or salinity may be present.
Failure to follow this instruction may result in fire or explosion.
5. Keep metal chip, dust, and wire residue from flowing into the unit.
Failure to follow this instruction may result in fire or product damage.
Ordering Information
T
CN
4 S
2 4 R
P
No-mark Bolt wiring method
Wiring method
P
Connector plug connection method
Control output
R
Relay contact + SSR drive output
2
24VAC 50/60Hz, 24-48VDC
Power supply
4
100-240VAC 50/60Hz
Sub output
2
Alarm1 + Alarm2 output
S
DIN W48 × H48mm
M
DIN W72 × H72mm
Size
H
DIN W48 × H96mm
L
DIN W96 × H96mm
Digit
4
9999 (4 digit)
Setting type
CN
Dual display type, set by touch switch
Item
T
Temperature controller
1: Only for TCN4S model.
2: In case of the AC voltage model, SSR drive output method (standard ON/OFF control, cycle
control, phase control) is available to select.
※ The above specifications are subject to change and some models may be discontinued
without notice.
※ Be sure to follow cautions written in the instruction manual and the technical descriptions
(catalog, homepage).
Specification
Series
TCN4S
TCN4M
TCN4H
Power
AC Power
100-240VACᜠ 50/60Hz
supply
AC/DC Power 24VACᜠ 50/60Hz, 24-48VDCᜡ
Allowable voltage range 90 to 110% of rated voltage
AC Power
Max. 5VA(100-240VAC 50/60Hz)
Power
consumption
AC/DC Power Max. 5V(24VAC 50/60Hz), Max. 3W(24-48VDC)
Display method
7 segment (PV: red, SV: green), other display part(green, red) LED method
PV(W×H)
7.0×15.0mm
9.5×20.0mm
7.0×14.6mm
Character
size
SV(W×H)
5.0×9.5mm
7.5×15.0mm
6.0×12.0mm
RTD
DIN Pt100Ω, Cu50Ω (Allowable line resistance max.5Ω per a wire)
Input
type
TC
K(CA), J(IC), L(IC), T(CC), R(PR), S(PR)
Display
RTD
At room temperature(23ºC ± 5ºC): (PV ± 0.5% or ±1ºC, select the higher one) ± 1 digit
accuracy
Out of room temperature range: (PV± 0.5% or ±2ºC, select the higher one)± 1digit
TC
1
For TCN4S- -P, add ±1℃ by accuracy standard.
Control
Relay
250VACᜠ 3A 1a
output
SSR
12VDCᜡ±2V 20mA Max.
Alarm output
AL1, AL2 Relay: 250VACᜠ 1A 1a
Control method
ON/OFF control, P, PI, PD, PID control
1 to 100℃/℉ (0.1 to 50.0℃/℉)
Hysteresis
Proportional band(P)
0.1 to 999.9ºC/℉
Integral time(I)
0 to 9999 sec.
Derivative time(D)
0 to 9999 sec.
Control period(T)
0.5 to 120.0 sec.
Manual reset
0.0 to 100.0%
Sampling period
100ms
AC power
2000VAC 50/60Hz 1min.(between input terminal and power terminal)
Dielectric
strength
AC/DC power 1000VAC 50/60Hz 1min.(between input terminal and power terminal)
Vibration
0.75mm amplitude at frequency of 5 to 55Hz in each X, Y, Z direction for 2 hours
Mechanical OUT: Over 5,000,000 times, AL1/2: Over 5,000,000 times
Relay life
OUT: Over 200,000 times(250VAC 3A resistive load)
cycle
Electrical
AL1/2: Over 300,000 times(250VAC 1A resistive load)
Insulation resistance
Min. 100MΩ(at 500VDC megger)
Noise
Square-wave noise by noise simulator(pulse width 1㎲) ±2KV R-phase and S-phase
Memory retention
Approx. 10 years (when using non-volatile semiconductor memory type)
Ambient temp. -10 to 50ºC, Storage: -20 to 60ºC
Environ
-ment
Ambient humi. 35 to 85%RH, Storage: 35 to 85%RH
Double insulation or reinforced insulation (mark:
Insulation type
the measuring input part and the power part : AC power 2kV, AC/DC power 1kV)
Approval
Approx. 147g
Approx. 203g
Approx. 194g
Weight
2
(approx. 100g)
(approx. 133g)
(approx. 124g)
1:
At room temperature(23ºC±5ºC)
— Below 200ºC of thermocouple R(PR), S(PR) is (PV ±0.5% or ±3ºC, select the higher one) ±1 digit
— Over 200ºC of thermocouple R(PR), S(PR) is (PV ±0.5% or ±2ºC, select the higher one) ±1 digit
— Termocouple L (IC), RTD Cu50Ω is (PV ±0.5% or ±2ºC, select the higher one) ±1 digit
Out of room temperature range
— Below 200ºC of thermocouple R(PR), S(PR) is (PV ±1.0% or ±6ºC, select the higher one) ±1 digit
— Over 200ºC of thermocouple R(PR), S(PR) is (PV ±0.5% or ±5ºC, select the higher one) ±1 digit
— Thermocouple L(IC), RTD Cu50Ω is (PV ±0.5% or ±3ºC, select the higher one) ±1 digit
For TCN4S- -P, add ±1℃ by accuracy standard.
2: The weight includes packaging. The weight in parentheses is for unit only.
Environment resistance is rated at no freezing or condensation.
Unit Description
1. Present temperature (PV) display (Red)
1) RUN mode: Present temperature (PV) display
2) Parameter setting mode: Parameter display
2. Set temperature (SV) display (Green)
1) RUN mode: Set temperature (SV) display
1
2) Parameter setting mode
: Parameter setting value display
3. Control/Alarm output display indicator
8
1) OUT: It turns ON when the control output is ON.
3
During SSR drive output type in CYCLE/
2
PHASE control, this indicator turns ON when
7
MV is over 3.0%.
4
2) AL1/AL2: It turns ON when the alarm output is ON.
5
4. Auto tuning indicator
AT indicator flashes by every 1 sec during operating
auto tuning.
5.
key
6
Used when entering into parameter groups,
returning to RUN mode, moving parameter, and saving
setting values.
6. Adjustment
Used when entering into set value change mode, digit moving and digit up/down.
1
7. Digital input key
2
Press
keys for 3 sec. to operate the set function
(RUN/STOP, alarm output reset, auto tuning) in digital input key [DI-T].
8. Temperature unit (
/℉) indicator
ºC
It shows current temperature unit.
Input Sensor and Temperature Range
Input sensor
Display
Temperature range(
-50 to 1200
KCaH
K(CA)
-50.0 to 999.9
KCaL
JIcH
-30 to 800
J(IC)
JIcL
-30.0 to 800.0
-40 to 800
LIcH
Thermocouple
L(IC)
-40.0 to 800.0
LIcL
TCcH
-50 to 400
T(CC)
TCcL
-50.0 to 400.0
R(PR)
0 to 1700
RPR
S(PR)
0 to 1700
SPR
DPtH
-100 to 400
DPt100Ω
-100.0 to 400.0
DPtL
RTD
-50 to 200
CUsH
Cu50Ω
CUsL
-50.0 to 200.0
Dimensions
TCN4L
TCN4S Series
48
6
64.5
11.0×22.0mm
7.0×14.0mm
TCN4H Series
6
64.5
48
Bracket
TCN4S Series
TCN4M, TCN4H, TCN4L Series
31
48.6
20
5
45
, dielectric strength between
15
21
Approx. 275g
55
(approx. 179g)
56
Connections
1)TCN4S Series
AL1 OUT
SSR
250VAC
OUT
※1
1A 1a
AL2 OUT
250VAC
1A 1a
Relay OUT
B’
250VAC
3A 1a
B
A
RTD
※2
SOURCE
2)TCN4S- -P
SSR
※1
OUT
Relay OUT
250VAC
3A 1a
※2
SOURCE
ºC
) Temperature range(℉)
※ TCN4 Series has selectable control output; Relay output, and
-58 to 2192
SSR drive output. AC/DC voltage type does not have SSRP
-58.0 to 999.9
function.
※1: 12VDC±2V 20mA Max.
-22 to 1472
※2: AC voltage type: 100-240VAC 5VA 50/60Hz
-22.0 to 999.9
AC/DC voltage type: 24VAC 5VA 50/60Hz
-40 to 1472
24-48VDC 3W
(unit: mm)
-40 to 999.9
※Use crimp terminals or teminals of size specified below.
Terminal
a
-58 to 752
a
b
c
number
-58.0 to 752.0
1 to 8
6
Max. 1.7 Max. 3.7
c
b
32 to 3092
9 to 11
6 to 8 Max. 2.1 Max. 4.2
<Crimp terminal>
12 to 14 6 to 8 Max. 1.5 Max. 3.5
32 to 3092
-148 to 752
a b
a b
-148.0 to 752.0
<Round>
<Forked>
-58 to 392
a
Min. 3.0
Min. 3.0
-58.0 to 392.0
b
Max.5.8
Max.5.8
TCN4S- -P
6
56
11.5
48
1.7
TCN4L Series
96
6
64.5
Panel cut-out
A
C
46
Size
A
B
C
D
Series
TCN4S
Min. 65
Min. 65
45
45
0.6
0
TCN4M
Min. 90
Min. 90
68
68
0.7
0
12
TCN4H
Min. 65
Min. 115
45
0.6
92
0
23.9
TCN4L
Min. 115
Min. 115
92
92
0.8
0
Parameter Groups
3)TCN4M Series
1. All Parameter
Please any key among
,
,
,
SV setting
Parameter 1group
AL1 OUT
SSR
250VAC
OUT
※1
1A 1a
AL1 alarm termerature
TC
AL2 OUT
250VAC
1A 1a
AL2 alarm termerature
Relay OUT
B’
250VAC
3A 1a
B
+
TC
A
+
RTD
SOURCE
※2
4)TCN4H/L Series
AL1 OUT
250VAC
1A 1a
AL2 OUT
250VAC
1A 1a
B’
B
TC
A
RTD
AL1 OUT
250VAC
SSR
1A 1a
※1
OUT
AL2 OUT
Press
key over 3 sec in any parameter group, it saves the set value and returns to RUN mode.
250VAC
Relay OUT
1A 1a
(Exception: Press
250VAC
If no key entered for 30 sec., it returns to RUN mode automatically and the set value of parameter
TC
RTD
3A 1a
B’
is not be saved.
Press
key again within 1 sec. after returning to RUN mode, it advances of the first parameter
B
of previous parameter group.
A
Press
key to move next parameter.
Parameter marked in
Set parameter as ‘Parameter 2 group → Parameter 1 group → Setting group of set value’ order
SOURCE
※2
considering parameter relation of each setting group.
1: It is not displayed for AC/DC power model (TCN4 -22R).
(unit: mm)
TCN4M Series
72
6
64.5
Terminal cover(sold separately)
RSA-COVER(48×48mm)
RMA-COVER(72×72mm)
70
3
48.4
9.8
22.5
RHA-COVER(48×96mm)
RLA-COVER(96×96mm )
47.2
4
94
3
0.6
0
0.7
0
0.8
0
0.8
0
Run mode
2sec.
4sec.
Parameter 2group
PAR1
PAR2
Input
Temperature
Input
Input
sensor
unit
correction
digital filter
AL1
IN-T
UNIT
IN-B
MAvF
AL2
Control output
SV high-
SV low-limit
Control type
operation
limit value
value
Auto tunung
C-MD
O-FT
H-SV
L-SV
AT
Proportional band
SSR drive output
Control output
Control
AL1 alarm
method
※1
P
type
cycle
operation mode
OUT
SSrM
T
AL-1
Integral time
I
LBA detection
LBA
Alarm output
AL2 alarm
band
monitoring time
hysteresis
operation mode
Derivative time
LBaT
AHYS
AL-2
LBaB
D
Manual reset
REST
Digital input
Control output MV in case
Parameter
key
of input break error
lock
DI-K
ErMV
LOC
Hysteresis
HYS
3sec.
3sec.
key once in SV setting group, it returns to RUN mode).
might not be displayed depending on other parameter settings.
2. Parameter 2group
key: Moves parameter and saves the set,
or
key: Changes the set
Parameter
Display
Description
Setting range: Refer to ‘ Input Sensor And Temperature Range’.
Input sensor
If changing input sensor, SV, IN-B, H-SV, L-SV, AL1, AL2, LBaT,
IN-T
LBaB, AHYS parameter values are initialized.
?C
?F
Temperature unit UNIT
If changing temperature unit, SV, IN-B, H-SV, L-SV, AL1, AL2,
LBaT, LBaB, AHYS parameter values are initialized.
Setting range
Input correction
● KCaH, JIcH, LIcH, TCcH, RPR, SRP, DPtH, CUsH:-999 to 999℃/℉
IN-B
● KCaL, JIcL, LIcL, TCcL, DPtL, CUsL: -199.9 to 999.9℃/℉
Input digital filter
Setting range: 0.1 to 120.0 sec.
MAvF
Setting range: Within the rated temperature range by input
sensor[
When changing SV lower limit value, if SV
L-SV, SV is initialized as L-SV.
SV low-limit value L-SV
In case of changing input sensor type[IN-T], it changes automatically as min.
value of the changed input sensor.
Setting range: Within the rated temperature range by input sensor[ H-SV
SV high-limit
When changing SV higher limit value, if SV
H-SV, SV is initialized as
H-SV
value
In case of changing input sensor type [IN-T], it changes automatically as
max. value of the changed input sensor.
Control output
HEAT
COOL
O-FT
operation
When changing control output operation, ErMV is initialized.
PID
ONOF
Control type
When changing control type, ErMV is initialized (control output MV is
C-MD
below 100%) and DI-T turns OFF automatically.
Control output type
OUT
RLY
SSR
STND
CYCL
PHAS
SSR drive output
SSrM
It is displayed when selecting control output [OUT] as [SSR].
method
It is not displayed for AC/DC power model (TCN4 -22R).
Setting range: 0.5 to120.0 sec.
In case of Relay drive output [RLY] of control output [OUT], it is set as
Control cycle
T
20.0 sec. In case of SSR drive output [SSR] of that, it is set as 2.0 sec.
T is not displayed when SSR drive output [SSR.M] method is set as CYCL, PHAS.
AL1 alarm
AM)_
AM!A
AM@A
AM^A
SBaA
AL-1
operation mode
SBaB
SBaA
LBaB
AM!A
AM!B
AM!C
AM!D
AM!E
AL2 alarm
AL-2
For more details refer to
Functions 6. Alarm.
operation mode
Black: Flashes, Gray: Fixed
When changing AL1, AL2 alarm operation mode, AL1, AL2 alarm
temperature value are initialized.
Setting range: Refer to
Functions 4. Alarm output hysteresis.
Alarm output
is not displayed when AL1, AL2 alarm operation mode [AL-1,
AHYS
AHYS
hysteresis
AL-2] is set as [AM0._,
,
].
SBa
LBa
Setting range: 0 to 9999 sec.
LBA monitoring
‘0’ is set, loop break alarm function is OFF.
LBaT
time
is displayed when AL1, AL2 alarm operation mode [AL-1,
LBaT
AL-2] is set as
LBa
.
Setting range: 0 to 999(0.0 to 999.9)
, ‘0’ is set, loop break alarm function is OFF.
LBA monitoring
is displayed when AL1, AL2 alarm operation mode [AL-1,
LBaB
LBaB
range
AL-2] is set as
LBa
and
LBaT
is not ‘0’.
STOP
AlRE
AT
OFF
Press
keys for 3 sec. and it executes the set function.
Digital input key
DI-K
For more information, refer to
Functions 5. Digital input key.
When control type [C-MD] is ONOF, AT is not displayed.
Setting range 0.0 to 100.0%
Control output
Only 0.0, 100% are displayed when control type [C-MD] is set as ONOF.
MV in case of
ErMV
When changing PID control to ON/OFF control, if MV is below
input break error
100.0%, it is initialized as 0.0%.
OFF
LOC1
LOC2
LOC3
LOC1: Locks parameter 2 group, LOC2: Locks parameter 1, 2 group
Parameter lock
LOC
LOC3: Locks parameter 1, 2 group and SV setting
Parameter setting values are still possible to check when parameter lock is set.
key: Moves parameter and saves the set,
3. Parameter 1 group
key: Moves digit,
or
key: Changes the set
Parameter
Display
Description
Setting range: Deviation alarm(-F.S to F.S), Absolute value alarm(temperature range)
AL1 alarm temp.
AL1
In case alarm operation mode [AL-1, AL-2] of Parameter 2 group AM)_/
AL2 alarm temp.
AL2
, no parameters is displayed.
SBa
/
LBA
Auto tuning
Front AT indicator flashes during auto tuning operation.
AT
OFF
ON
Proportional band
Setting range: 0.1 to 999.9
P
Integral time
I
Setting range: 0 to 9999 sec. Integral operation is OFF when set value is «0».
Derivative time
D
Setting range: 0 to 9999 sec. Derivative operation is OFF when set value is «0».
Manual reset
Setting range: 0.0 to
100.0%/ It is displayed in P/PD control.
REST
Setting range
● KCaH, JIcH, LIcH, TCcH, RPR, SRP, DPtH, CUsH:
Hysteresis
HYS
● KCaL, JIcL, LIcL, TCcL, DPtL, CUsL:
0.1 to 50.0
It is displayed when control type [C-MD] of parameter 2 group is set ONOF.
4. SV setting
You can set the temperature to control with
keys.
Setting range is within SV lower limit value [L-SV] to SV higher limit value [H-SV].
E.g.) In case of changing set temperature from 210ºC to 250ºC
①RUN mode
Press any key among
,
,
,
once.
②SV setting mode
Change SV
by
,
,
keys
④Check SV
5. Parameter reset
Reset all parameters as factory default. Hold the front
+ +
keys for 5 sec., to enter parameter reset
[INIT] parameter. Select ‘YES’ and all parameters are reset as factory default. Select ‘NO’ and previous
settings are maintained. If setting parameter lock [LOC] or processing auto-tuning, parameter reset is
unavailable.
Functions
key: Moves digit,
1. Auto tuning [AT]
Auto tuning measures the control subject’s thermal characteristics and thermal response rate, and then
determines the necessary PID time constant. (When control type[C-MD] is set as PID, it is displayed.)
Application of the PID time constant realizes fast response and high precision temperature control.
If error [OPEN] occurs during auto tuning, it stops this operation automatically. To stop auto tuning,
change the set as [OFF]. (It maintains P, I, D values of before auto tuning.)
2. Hysteresis [HYS]
In case of ON/OFF control, set between ON and OFF intervals
as hysteresis. (When control type [C-MD] is set as ONOF, it
is displayed.) If hysteresis is too small, it may cause control
output hunting (takeoff, chattering) by external noise, etc.
L-SV
(H-SV-1digit)]
3. SSR drive output selection(SSRP function) [SSrM]
● SSRP function is selectable one of standard ON/OFF control, cycle control, phase control by utilizing
standard SSR drive output.
● Realizing high accuracy and cost effective temperature control as linear output(cycle control and
(L-SV+1digit)]
phase control).
H-SV.
● Select one of standard ON/OFF control [STND], cycle control [CYCL] , phase control [PHAS] at [SSrM]
parameter of parameter 2 group. For cycle control, connect zero cross turn-on SSR or random
turn-on SSR. For phase control, connect random turn-on SSR.
Temperature controller
(TCN4 series)
SSR drive output
(12VDC)
Power
100-240VAC
50/60Hz
When selecting phase or cycle control mode, the power supply for load and temperature
LBaA
controller must be the same.
In case of selecting PID control type and phase [PHAS] / cycle [PHAS] control output modes, control
cycle [T] is not allowed to set.
LBaA
For AC/DC power model (TCN -22R), this parameter is not displayed and it is available only standard
control by relay or SSR.
AM!F
1)Standard ON/OFF control mode [STND]
A mode to control the load in the same way as Relay output type.
(ON: output level 100%, OFF: output level 0%)
AC
OUT
ON
OFF
ON
2)Cycle control mode [CYCL]
A mode to control the load by repeating output ON / OFF according to the rate of output within setting
cycle. Having improved ON / OFF noise feature by Zero Cross type.
AC
OUT
50Cycle
50%
3)Phase control mode [ PHAS]
A mode to control the load by controlling the phase within AC half cycle. Serial control is available.
RANDOM Turn-on type SSR must be used for this mode.
AC
OUT
10%
4. Alarm output hysteresis [AHYS]
It displays alarm output ON and OFF interval and hysteresis is applied to both AL1 OUT and AL2 OUT.
KCaH, JIcH, LIcH, TCcH, RPR, SPR, DPtH, CUsH: 1 to 100
KCaL, JIcL, LIcL, TCcL, DPtL, CUsL: 0.1 to 50.0
E.g.) AL1 alarm operation[AL-1]: AM#A
Temp.
AL1 alarm operation[AL1]: 10ºC
Alarm output hysteresis[AHYS]: 4 210ºC
SV 200ºC
1 to 100
190ºC
ON
AL1 OUT
OFF
210
5. Digital input key ( +
3sec.) [DI-K]
Parameter
Operation
OFF
OFF
It does not use digital input key function.
Pauses control output. Auxiliary output (except loop break alarm, sensor break alarm)
except Control output operates as setting. Hold the digital input keys for 3 sec. to restart.
t
t
t
RUN/STOP
STOP
③ Completes
SV setting
RUN
STOP
RUN
Clears alarm output by force.
(only when alarm option is alarm latch, or alarm latch and standby sequence 1/2
Clear alarm
AlRE
This function is applied when present value is out of alarm operation range but alarm
output is ON.
Alarm operates normally right after clearing alarm.
Starts/Stops auto-tuning. This function is same as auto-tuning[AT] of parameter 1 group.
(You can start auto-tuning [AT] of parameter 1 group and stop it by digital input key.)
Auto-tuning
※ This parameter
AT appears only when
control method
AT
is set as PID. When
control method
[C-MD]
parameter is changed as OFF.
Set both alarm operation and alarm option by combining.
6. Alarm
Alarm outputs are two and each one operates individually.
AM!A
When the current temperature is out of alarm range, alarm clears
Alarm
Alarm
automatically. If alarm option is alarm latch or alarm latch and standby
operation
option
sequence 1/2, press digital input key( +
key[DI-K] of parameter 2 group set as AlRE), or turn OFF the power
1)Alarm operation
and turn ON to clear alarm.
Mode
Name
Alarm operation
AM)_
—
—
Heating operation
OFF
H
ON
Deviation
ON
OFF
high-limit
AM!
SV
PV
Hysteresis
alarm
100℃
110℃
High deviation: Set as 10℃
[HYS]
Temperature
ON
H
OFF
Deviation
SV
low-limit
AM@
PV
SV
alarm
90℃
100℃
Lower deviation: Set as 10℃
Deviation
ON
H
high/low-
AM#
limit
PV
90℃
alarm
High/Lower deviation: Set as 10℃
Deviation
OFF
H
high/low-
AM$
limit
PV
SSR Module
reserve
90℃
Load
High/Lower deviation: Set as 10℃
alarm
OFF
H
ON
Absolute
value high
PV
SV
AM%
90℃
100℃
limit alarm
Absolute-value Alarm:
Set as 90℃
ON
H
OFF
Absolute
AM^
value low
PV
SV
90℃
100℃
limit alarm
Absolute-value Alarm:
Set as 90℃
Sensor
SBa
—
break alarm
Loop break
LBa
—
alarm
※ H: Alarm output hysteresis[AHYS]
2)Alarm opetion
Option Name
Description
Standard
If it is an alarm condition, alarm output is ON. If it is a clear alarm condition, alarm output
AM .A
alarm
is OFF.
If it is an alarm condition, alarm output is ON and maintains ON status.
AM .B
Alarm latch
(Alarm output HOLD)
OFF
First alarm condition is ignored and from second alarm condition, standard alarm
Standby
AM .C
operates. When power is supplied and it is an alarm condition, this first alarm condition
sequence 1
is ignored and from the second alarm condition, standard alarm operates.
Alarm latch
If it is an alarm condition, it operates both alarm latch and standby sequence. When
and standby
power is supplied and it is an alarm condition, this first alarm condition is ignored and
AM .D
sequence 1
from the second alarm condition, alarm latch operates.
First alarm condition is ignored and from second alarm condition, standard alarm
Standby
operates. When re-applied standby sequence and if it is alarm condition, alarm output
AM .E
sequence 2
does not turn ON. After clearing alarm condition, standard alarm operates.
Basic operation is same as alarm latch and standby sequence1. It operates not only by
Alarm latch
50Cycle
power ON/OFF, but also alarm setting value, or alarm option changing. When re-applied
AM .F
and standby
standby sequence and if it is alarm condition, alarm output does not turn ON. After
80%
sequence 2
clearing alarm condition, alarm latch operates.
Condition of re-applied standby sequence for standby sequence 1, alarm latch and standby sequence 1: Power ON
Condition of re-applied standby sequence for standby sequence 2, alarm latch and standby sequence 2: Power ON,
changing set temperature, alarm temperature (AL1, AL2) or alarm operation (AL-1, AL-2), switching STOP mode
to RUN mode.
3)Sensor break alarm
The function that alarm output will be ON when sensor is not connected or when sensor’s disconnection
is detected during temperature controlling. You can check whether the sensor is connected with buzzer
or other units using alarm output contact. It is selectable between standard alarm [SBaA] or alarm latch
[SBaB].
50%
4)Loop break alarm(LBA)
It checks control loop and outputs alarm by temperature change of the subject. For heating
control(cooling control), when control output MV is 100%(0% for cooling control) and PV is not
increased over than LBA detection band [LBaB] during LBA monitoring time [LBaT], or when control
output MV is 0%(100% for cooling control) and PV is not decreased below than LBA detection band
[LBaB] during LBA monitoring time [LBaT], alarm output turns ON.
AHYS: 4
PV
AHYS: 4
Time
206
190
194
Start control
When control output MV is 100%, PV is increased over than LBA detection band [LBaB] during
to
LBA monitoring time [LBaT].
to
The status of changing control output MV (LBA monitoring time is reset.)
Digital input key
t
(t: over 3 sec.)
When control output MV is 0% and PV is not decreased below than LBA detection band [LBaB]
to
during LBA monitoring time [LBaT], loop break alarm (LBA) turns ON after LBA monitoring time.
STOP
RUN
to
Control output MV is 0% and loop break alarm (LBA) turns and maintains ON.
to
The status of changing control output MV (LBA monitoring time is reset.)
.)
When control output MV is 100% and PV is not increased over than LBA detection band [LBaB]
to
during LBA monitoring time [LBaT], loop break alarm (LBA) turns ON after LBA monitoring time.
When control output MV is 100% and PV is increased over than LBA detection band [LBaB] during
to
LBA monitoring time [LBaT], loop break alarm (LBA) turns OFF after LBA monitoring time.
to
The status of changing control output MV (LBA monitoring time is reset.)
[C-MD]
parameter 2 group
When executing auto-tuning, LBA detection band[LBaB] and LBA monitoring time are automatically set
parameter 2 group
is set as ONOF, this
based on auto tuning value. When alarm operation mode [AL-1, AL-2] is set as loop break alarm(LBA)
[LBa ], LBA detection band [LBaB] and LBA monitoring time [LBaT] parameter is displayed.
7. Manual reset[REST]
When selecting P/PD control mode, certain temperature
difference exists even after PV reaches stable status because
heater’s rising and falling time is inconsistent due to thermal
3 sec., digital input
characteristics of controlled objects, such as heat capacity,
heater capacity. This temperature difference is called offset
and manual reset [REST] function is to set/correct offset.
Description
When PV and SV are equal, reset value is 50.0%. After control
No alarm output
is stable, PV is lower than SV, reset value is over 50.0% or PV
If deviation between PV and SV
OFF
H
ON
is higher than SV, reset value is below 50.0%.
as high-limit is higher than set
8. Input correction[IN-B]
PV
SV
value of deviation temperature,
Controller itself does not have errors but there may be error by external input temperature sensor.
90℃
100℃
the alarm output will be ON.
High deviation: Set as -10℃
This function is for correcting this error.
If deviation between PV and SV
E.g.) If actual temperature is 80ºC but controller displays 78ºC, set input correction value [IN-B] as
ON
H
OFF
‘002’ and controller displays 80ºC.
as low-limit is higher than set
SV
PV
value of deviation temperature,
As the result of input correction, if current temperature value (PV) is over each temperature range
100℃
110℃
the alarm output will be ON.
of input sensor, it displays ‘HHHH’ or ‘LLLL’.
Lower deviation: Set as -10℃
9. Input digital filter[MAvF]
OFF
H
ON
If deviation between PV and SV
If current temperature (PV) is fluctuating repeatedly by rapid change of input signal, it reflects to MV
as high/low-limit is higher than set
and stable control is impossible. Therefore, digital filter function stabilizes current temperature value.
SV
PV
value of deviation temperature,
100℃
110℃
For example, set input digital filter value as 0.4 sec, and it applies digital filter to input values during 0.4
the alarm output will be ON.
sec and displays this values. Current temperature may be different by actual input value.
ON
H
OFF
If deviation between PV and SV
10. Error
as high/low-limit is higher than set
Display
Description
SV
PV
value of deviation temperature,
100℃
110℃
the alarm output will be OFF.
OPEN
Flashes if input sensor is disconnected or sensor is not connected. Check input sensor state.
Flashes if measured sensor input is higher than temperature range. When input is within the rated
HHHH
OFF
H
ON
LLLL
Flashes if mesured sensor input is lower than temperature range
If PV is higher than the absolute
SV
PV
value, the output will be ON.
100℃
110℃
Absolute-value Alarm:
Factory Default
Set as 110℃
1. SV setting
ON
H
OFF
Parameter Default
If PV is lower than the absolute
SV
PV
value, the output will be ON.
—
100℃
110℃
Absolute-value Alarm:
2. Parameter 1 group
Set as 110℃
It will be ON when it detects
Parameter Default
sensor disconnection.
AL1
1250
It will be ON when it detects loop
AL2
1250
break.
3. Parameter 2 group
Parameter Default
IN-T
KCaH
UNIT
?C
IN-B
0000
MAvF
00)1
L-SV
-050
The AC/DC voltage models do not have SSR drive output method[SSrM]. In case of control output
[ OUT] , if set as SSR, it supports only ON/OFF output.
Installation
TCN4S(48×48mm) Series
Insert product into a panel, fasten bracket by pushing with tools as shown above.
Cautions during Use
1. Follow instructions in ‘Cautions during Use’. Otherwise, It may cause unexpected accidents.
2. Check the polarity of the terminals before wiring the temperature sensor.
For RTD temperature sensor, wire it as 3-wire type, using cables in same thickness and length.
For thermocouple (CT) temperature sensor, use the designated compensation wire for extending wire.
3. Keep away from high voltage lines or power lines to prevent inductive noise.
In case installing power line and input signal line closely, use line filter or varistor at power line and
shielded wire at input signal line.
Do not use near the equipment which generates strong magnetic force or high frequency noise.
4. Install a power switch or circuit breaker in the easily accessible place for supplying or disconnecting
the power.
5. Do not use the unit for other purpose (e.g. voltmeter, ammeter), but temperature controller.
6. When changing the input sensor, turn off the power first before changing.
After changing the input sensor, modify the value of the corresponding parameter.
7. 24VAC, 24-48VDC power supply should be insulated and limited voltage/current or Class 2, SELV
power supply device.
8. Make a required space around the unit for radiation of heat.
Time
For accurate temperature measurement, warm up the unit over 20 min after turning on the power.
9. Make sure that power supply voltage reaches to the rated voltage within 2 sec after supplying power.
10. Do not wire to terminals which are not used.
11. This unit may be used in the following environments.
①Indoors (in the environment condition rated in ‘Specifications’)
③Pollution degree 2
Major Products
Photoelectric Sensors
Fiber Optic Sensors
Door Sensors
Door Side Sensors
Area Sensors
Proximity Sensors
Pressure Sensors
Rotary Encoders
Connector/Sockets
Switching Mode Power Supplies
Control Switches/Lamps/Buzzers
I/O Terminal Blocks & Cables
Stepper Motors/Drivers/Motion Controllers
Graphic/Logic Panels
Field Network Devices
Laser Marking System (Fiber, Co₂, Nd: YAG)
Laser Welding/Cutting System
·Manual reset [REST] by control result
Set below 50.0 as reset value
Offset
SV
Offset
Set over 50.0 as reset value
Measured value
Troubleshooting
temperature range, this display
disappears.
0
Parameter Default
Parameter Default
Parameter Default
AT
OFF
I
0000
REST
05)0
P
01)0
D
0000
HYS
002
Parameter Default
Parameter Default
Parameter Default
H-SV
1200
T
02)0
LBaB
0002
O-FT
HEAT
AL-1
AMiA
DI-K
STOP
C-MD
PID
LA-2
Am@A
ErMV
00)0
OUT
RLY
AHYS
001
LOC
OFF
SSrM
STND
LBaT
0000
Other Series
②Altitude max. 2,000m
④Installation category II
Temperature Controllers
Temperature/Humidity Transducers
SSRs/Power Controllers
Counters
Timers
Panel Meters
Tachometer/Pulse (Rate) Meters
Display Units
Sensor Controllers